XHV2 (GV2) Pemutus sirkuit perlindungan motor
Model No.lan tegese
Model produk | Rated saiki InA | Arus komuter kisaran pangaturan kanggo koponen A. | Nilai komuter saiki sing disjointing ing lapangan instan InA | Urutan No. |
GV2-M(ME) | 0.16 | 0.1-0.16 | 1.5 | XHV2-32(GV2)-M01C |
0.25 | 0.16-0.25 | 2.4 | XHV2-32(GV2)-M02C | |
0.4 | 0.25-0.4 | 5 | XHV2-32(GV2)-M03C | |
0.63 | 0.4-0.63 | 8 | XHV2-32(GV2)-M04C | |
1 | 0.63-1 | 13 | XHV2-32(GV2)-M05C | |
1.6 | 1-1.6 | 22.5 | XHV2-32(GV2)-M06C | |
2.5 | 1.6-2.5 | 33,5 | XHV2-32(GV2)-M07C | |
4 | 2.5-4 | 51 | XHV2-32(GV2)-M08C | |
6.3 | 4-6.3 | 78 | XHV2-32(GV2)-M10C | |
10 | 6-10 | 138 | XHV2-32(GV2)-M14C | |
14 | 9-14 | 170 | XHV2-32(GV2)-M16C | |
18 | 13-18 | 223 | XHV2-32(GV2)-M20C | |
23 | 17-23 | 327 | XHV2-32(GV2)-M21C | |
25 | 20-25 | 327 | XHV2-32(GV2)-M22C | |
32 | 24-32 | 416 | XHV2-32(GV2)-M32C |
XHV2(GV2) Pemutus sirkuit proteksi motor | Tabel 1 | ||||
XHV2(GV2)-M(ME)(P) | XHV2(GV2)-RS | XHV2(GV2)-PM | |||
M01C | 0.1-0.16 | RS01C | 0.1-0.16 | PM01C | 0.1-0.16 |
M02C | 0.16-0.25 | RS02C | 0.16-0.25 | PM02C | 0.16-0.25 |
M03C | 0.25-0.40 | RS03C | 0.25-0.40 | PM03C | 0.25-0.40 |
M04C | 0.40-0.63 | RS04C | 0.40-0.63 | PM04C | 0.40-0.63 |
M05C | 0.63-1 | RS05C | 0.63-1 | PM05C | 0.63-1 |
M06C | 1-1.6 | RS06C | 1-1.6 | PM06C | 1-1.6 |
M07C | 1.6-2.5 | RS07C | 1.6-2.5 | PM07C | 1.6-2.5 |
M08C | 2.5-4 | RS08C | 2.5-4 | PM08C | 2.5-4 |
M10C | 4-6.3 | RS10C | 4-6.3 | PM10C | 4-6.3 |
M14C | 6-10 | RS14C | 6-10 | PM14C | 6-10 |
M16C | 9-14 | RS16C | 9-14 | PM16C | 9-14 |
M18C | 10-16 | RS18C | 10-16 | PM18C | 10-16 |
M20C | 13-18 | RS20C | 13-18 | PM20C | 13-18 |
M21C | 17-23 | RS21C | 17-23 | PM21C | 17-23 |
M22C | 20-25 | RS22C | 20-25 | PM22C | 20-25 |
M32C | 24-32 | RS32C | 24-32 | PM32C | 24-32 |
Daya dirating saka telung fase electromotor kontrol dening breaker (GV2 Motor pangayoman circuit breaker) | Tabel 2 |
Range pangaturan arus pengenal yaiku (A) | Daya standar saka telung fase electromotor KW.AC-3, 50Hz/60Hz | |||||
230/240 V | 400V | 415V | 440V | 500V | 690V | |
0.1-0.16 | — | — | — | |||
0.16-0.25 | — | - | — | |||
0.25-0.40 | — | — | — | |||
0.4-0.63 | 一 | 一 | 0.37 | |||
0.63-1 | 0.37 | 0.37 | 0.55 | |||
1-1.6 | 0.37 | 0.55 | 0.75 | 1.1 | ||
1.6-2.5 | 0.37 | 0.75 | 0.75 | 1.1 | 1.1 | 1.5 |
2.5-4 | 0.75 | 1.5 | 1.5 | 1.5 | 2.2 | 3 |
4-6.3 | 1.1 | 2.2 | 2.2 | 3 | 3.7 | 4 |
6-10 | 2.2 | 4 | 4 | 4 | 5.5 | 7.5 |
9-14 | 3 | 5.5 | 5.5 | 7.5 | 7.5 | 9 |
13-18 | 4 | 7.5 | 9 | 9 | 9 | 11 |
17-23 | 5.5 | 11 | 11 | 11 | 11 | 15 |
20-25 | 5.5 | 11 | 11 | 11 | 15 | 18.5 |
24-32 | 7.5 | 15 | 15 | 15 | 18.5 | 23 |
Nilai komuter arus disjointing saka breaker ing medan magnet instan. (Deleng tabel 3) Tabel 3 | ||
Rated saiki InA | Arus komuter kisaran pangaturan kanggo koponen A. | Nilai komuter saiki sing disjointing ing lapangan instan InA |
0.16 | 0.1-0.16 | 1.5 |
0.25 | 0.16-0.25 | 2.4 |
0.4 | 0.25-0.4 | 5 |
0.63 | 0,4-0,63 | 8 |
1 | 0.63-1 | 13 |
1.6 | 1-1.6 | 22.5 |
2.5 | 1.6-2.5 | 33.5 |
4 | 2.5-4 | 51 |
6.3 | 4-6.3 | 78 |
10 | 6-10 | 138 |
14 | 9-14 | 170 |
18 | 13-18 | 223 |
23 | 17-23 | 327 |
25 | 20-25 | 327 |
32 | 24-32 | 416 |
Aksesoris (waca tabel 4)
Jeneng aksesoris | Kode | jinis kontak | panggonan instalasi | |
Kontak bantu instan | AE1 | 11NO/1NC | 1 PCS) ngarep breaker (1 PCS bisa diinstal) | |
AE11 | 11NO+1NC | |||
AE20 | 22 NO | |||
AN11 | 11NO+1NC | sisih kiwa breaker (4PCS bisa diinstal) | ||
AN20 | 22 NO | |||
kontak sinyal fault Kontak bantu cepet | AD1010 | Masalah mbukak terus-terusan | NO | |
AD1001 | NC | |||
AD0110 | Masalah sing terus-terusan ditutup | N. | ||
AD0101 | NC | |||
Kontak short circuit | AM11 | 1 NO, 1NC |
4.1 Kontak aksesoris
Tabel 4
4.2 Tabel pamisah listrik 5 | |||||
Jeneng aksesoris | Kode | Tegangan | panggonan instalasi | ||
Lack-voltase disjointing | AU115 | 110-127V 50Hz | Hak breaker (1 PCS bisa diinstal) | ||
AU225 | 220-240V 50Hz | ||||
AU385 | 380-415V 50Hz | ||||
Divisi disjoining | AS115 | 110-127V 50Hz | |||
AS225 | 220-240V 50Hz | ||||
AS385 | 380-415V 50Hz | ||||
Digunakake kanggo ngeculake voltase sithik | AX115 | 110-127V 50Hz | |||
AX225 | 220-240V 50Hz | ||||
AX385 | 380-415V 50Hz | ||||
4.3 Kasus pelindung saka breaker Tabel 6 | |||||
Jeneng aksesoris | Kelas perlindungan kasus | Kode | Memo | ||
Cangkang instalasi njaba | aku p41 | MC01 | |||
aku p55 | MC02 | ||||
aku p65 | MC03 |
Dimensi fiksasi eksternal
5.1 Njelaske nganggo bentuk garis lan mbenakake dimensi breaker (GV2 Motor proteksi sirkuit breaker) (deleng grafik2, 3).
5.2 Pemutus (pemutus sirkuit proteksi Motor GV2) nggunakake instalasi rel konduktor standar, rel konduktor kudu memenuhi standar instalasi tipe A2.1 TH35-7.5 JB6525.
5.3 Instalasi njaba saka GV2 Motor pangayoman circuit breaker (deleng grafik1.4).
4.12 Kurva karakteristik disjointing (deleng grafik 5) wektu kerja rata-rata miturut kelipatan arus komuter
Parameter teknis utama
1. Dirating voltase jampel Ui (V): 690;
2. Dirating voltase karya Ue (V): 230/240, 400/415, 440, 550, 690;
3. Dirating frekuensi Hz: 50/60;
4. Kelas dirating saiki saka Nihan Inm (A): 32;
5. Dirating voltase saka disjointer ln (A) (j41 Tabel 1);
6. Ing sawetara nyetel saka commuting saiki (A) (Tabel 1);
7. Kapasitas nglereni kanggo dirating watesan short circuit lcu (kA) (Tabel 7);
8. Kapasitas nglereni kanggo dirating karya short circuit lcs(kA)(Tabel 7);
9. Tegangan ditanggung kanggo dirating kejut Uimp (V): 8000o
Karakteristik proteksi aksi over-current.
Tabel 7
Rated saiki ln(A) | Nyetel nesu saka commuting saiki | ICS Kapasitas pemotongan kanggo leu sirkuit cendhak sing dirating, kapasitas nglereni kanggo sirkuit cendhak sing dirating | Jarak busur (mm) | |||||||||
230/240 V | 400/415V | 440V | 500V | 690V | ||||||||
lcu (kA) | lcs (kA) | lcu (kA) | lcs (kA) | lcu (kA) | lcs (kA) | lcu (kA) | lcs (kA) | lcu (kA) | lcs (kA) | |||
0.16 | 0.10-0.16 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 40 |
0.25 | 0.16-0.25 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 40 |
0.4 | 0.25-0.4 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 40 |
0.63 | 0.4-0.63 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 40 |
1 | 0.63-1 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 40 |
1.6 | 1-1.6 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 40 |
2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 3 | 2.25 | 40 |
4 | 2.5-4 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 3 | 2.25 | 40 |
6.3 | 4-6.3 | 100 | 100 | 100 | 100 | 50 | 50 | 50 | 50 | 3 | 2.25 | 40 |
10 | 6-10 | 100 | 100 | 100 | 100 | 15 | 15 | 10 | 10 | 3 | 2.25 | 40 |
14 | 9-14 | 100 | 100 | 15 | 7.5 | 8 | 4 | 6 | 4.5 | 3 | 2.25 | 40 |
18 | 13-18 | 100 | 100 | 15 | 7.5 | 8 | 4 | 6 | 4.5 | 3 | 2.25 | 40 |
23 | 17-23 | 50 | 50 | 15 | 6 | 6 | 3 | 4 | 3 | 3 | 2.25 | 40 |
25 | 20-25 | 50 | 50 | 15 | 6 | 6 | 3 | 4 | 3 | 3 | 2.25 | 40 |
32 | 24-32 | 50 | 50 | 10 | 5 | 6 | 3 | 4 | 3 | 3 | 2.25 | 40 |
1 Karakteristik tumindak pemutus (pemutus sirkuit proteksi motor GV2) nalika saben beban fase seimbang.
Tabel 8
Kelipatan nilai saiki | Negara wiwitan | Wektu sing ditemtokake | Asil amarga | Suhu udara sekitar |
1.05 | kahanan kadhemen | tN2h | Ora disjointing | |
1.2 | Status panas (munggah nganti saiki sing ditemtokake sawise tes No 1) | t<2h | Disjointing | +40°C ±2°C |
1.5 | Arus komuter siji-wektu Diwiwiti sawise imbangan bot | t<2 min | Disjointing | |
7.2 | kahanan kadhemen | 2 | Disjointing |
2. Karakteristik tumindak pemutus (pemutus sirkuit proteksi motor GV2) nalika saben beban fase ana ing keseimbangan (fase-rusak).
Kelipatan nilai saiki | Negara wiwitan | Wektu sing ditemtokake | Asil amarga | Suhu udara sekitar | |
Sembarang rong fase | Fase katelu | ||||
1.0 | 0.9 | kahanan kadhemen | tw2h | Ora disjointing | +40°C ± 2°C |
1.15 | 0 | Status panas (munggah nganti saiki sing ditemtokake sawise tes No 1) | t<2h | Disjointing |